The project is titled ADA Compliant Main Lobby Entrance Vestibules. Twenty-four door leaves, two vestibules, a new curtain wall interface.
The electrical drawings call for a junction box for an automatic door opener at each vestibule, with power and low-voltage conduit landing on specific circuits. E-800 confirms two auto-door openers in the conduit bundle to each vestibule. The key note says to coordinate with the equipment vendor.
The architectural specification, 084113, describes the doors as manual-swing. The Table of Contents contains no automatic door operator section, no electrified hardware section, and no security section.
On a project named for ADA compliance, nothing in the bid documents says who furnishes the door operators.
Exposure ≈ $54,000 Every bidder on that job held the same documents and the same silence. The ones who caught it carried rough-in only and asked. The ones who didn't, guessed.